Repair Section
84
(4) Checking for gas leaks
1) Remove the charging hose (green) from the
vacuum pump, and connect the hose to the
refrigerant cylinder (R-410A).
2) Loosen the nut on the gauge manifold side of the
charging hose (green).
3) Open the valve of the refrigerant cylinder and
perform air purging in the charging hose (green).
Then tighten the nut.
4) Open the high-pressure valve of the gauge
manifold. Charge the system with refrigerant until
the high-pressure gauge indicates 57 psi (390
kPa). After charging is complete, close the high-
pressure valve.
5) Open the valve of the refrigerant cylinder and
perform air purging in the charging hose (green).
Then tighten the nut.
6) Check carefully for gas leaks inside the
refrigerant system using the gas leak tester.
7) Repair any leak.
WARNING
Any repair on a charged system should be
performed by a licensed professional only.
WARNING
Before checking for gas leaks, fully confirm
that there is nothing flammable in the area
to cause an explosion or fire. Contact of
refrigerant with an open fire generates
toxic gas.
I001901
Open The Valve
of Refrigerant
Cylinder
to Process Tube Fitting
Charging Hose
(Green)
Refrigerant
Cylinder R-410A
Red
LO
Closed
HI
Closed
Valve Setting
Air Purging
I002228
LO
Closed
HI
Open
LO
Closed
HI
Closed
Refrigerant
Cylinder R-410A
Valve Setting
Gauge Reading
57 psi
(390 k Pa)
Open High-Pressure
Valve
High-Pressure
Side Tube
Low-Pressure
Valve (Closed)
Process Tube Fitting
Refrigerant
Cylinder
Valve
(Open)