Repair Section
45
E09 E09
Evaporator fan motor
locked
4
ON
When a fan motor speed of
50 rpm or less is detected
four times within 10 seconds
after the fan motor is started.
E10 E10
Condenser fan motor
locked

OL OL Compressor overload 
When compressor overload
relay is activated.
E11 E11
STI module
communication error

When a communication failure
between the STI module and
microcomputer on the relay
board is detected for at least 40
seconds.
E12
E14
Compressor over
current

When compressor current is
detected at or above 35.9 A.
E15
Compressor lock
failure

During the operational check
when the compressor is
stopped, no change in position
is detected.
E16
Compressor phase
interruption abnormality

When one phase is detected
as 0 A.
E17
Motor position
detection abnormality

When an abnormality in the
compressor motor position is
detected.
E13
E18 Input overcurrent
When STI module input
current that exceeds the
specified value is detected.
E19
Power device
temperature
abnormality

When STI module
temperature that exceeds the
specified value is detected.
E20
DC voltage
abnormality

When a DC voltage or
current that is at or below the
specified value, or at or
above the specified value is
detected.
E21
Power device damage
abnormality

When a compressor startup
current/voltage that is at or
below the specified value is
detected.
E22 Circuit malfunction
When a short or open in the
STI internal current/voltage
detection circuit is detected.
Self-Diagnostic
Code
Cause
Alarm
Pattern
Relay Board
LED (Red)
Warning
Signal
Output
Detection Contents
User
Mode
Service
Mode
1 2 3 4 5 6