Operation Section
11
3. SPECIFICATIONS
3.1 Technical Specifications
ITEM SPECIFICATIONS
Electronic Features Control Millivolt Thermostat (Field supplied)
Electrical Characteristics Voltage Requirement Single-Phase, 115 V, 60 Hz
Operating Voltage
Range
Max. 127 V
Min. 104 V
Starting Current 50 A
Recommended Fuse Size 15 A
FLA 11.2 A
MCA 14.9 A
MOP 20 A
LRA 50 A
Cooling Capacity and Power Consumption
Evaporator: 80°F (27°C),
50% RH
Condenser: 95°F (35°C),
50% RH
Total Cooling Capacity
*1
10500 Btu/h (3090 W)
Sensible Cooling Capacity
*1
7200 Btu/h (2100 W)
Power Consumption
*1
1.23 kW
Current Consumption
*1
11.2 A
EER 8.5
Power Factor 96%
Evaporator: 72°F (22°C),
50% RH
Condenser: 95°F (35°C),
50% RH
Total Cooling Capacity
*1
9300 Btu/h (2730 W)
Sensible Cooling Capacity
*1
7000 Btu/h (2040 W)
Power Consumption
*1
1.22 kW
Current Consumption
*1
11.1 A
EER 7.6
Power Factor 96%
Compressor Type Hermetic Rotary
Output 0.91 kW
Evaporator Type of Evaporator Plate Fin
Type of Fan Centrifugal Fan
Air Flow High 324 CFM (550 m
3
/h)
Low 228 CFM (390 m
3
/h)
Max. External Static Pressure 0.16 IWG (40 Pa)
Motor Output High 0.04 kW
Low 0.01 kW