Repair Section
54
8.8 Inspection of Fan Motor
(1) Condenser fan motor
Measure resistance across the terminals of the
fan motor. (All terminals must be disconnected
from the unit.)
Between terminals (at 77 °F (25 °C))
- J6-CF11 Approx. 3.5 ohm
- J6-CF12 Approx. 6.0 ohm
- CF11-CF12 Approx. 9.1 ohm
If the measured resistance is not equal to these
standard values, replace the fan motor.
(2) Evaporator fan motor
Measure resistance across the terminals of the
fan motor. (All terminals must be disconnected
from the unit.)
Between terminals (at 77 °F (25 °C))
- J8-CF21 Approx. 7.6 ohm
- J8-CF22 Approx. 10.4 ohm
- CF21-CF22 Approx. 17.7 ohm
If the measured resistance is not equal to these
standard values, replace the fan motor.
8.9 Inspection of Compressor Motor
Measure resistance across the terminals of the
compressor motor. (All terminals must be
disconnected from the unit.)
Between terminals (at 77 °F (25 °C))
- R-C Approx. 0.4 ohm
- C-S Approx. 0.6 ohm
- S-R Approx. 0.9 ohm
If the measured resistance is not equal to these
standard values, replace the compressor. The
overload relay is internal to the compressor.
I001775
Condenser Fan Motor
Ground (Green/Yellow)
J5 Low (Red)
CF12 (Brown/White)
CF11 (White or Orange)
J6 High (Black)
I001774
Evaporator Fan Motor
Ground (Green/Yellow)
J7 Low (Red)
CF22 (Brown/White)
CF21 (White)
J8 High (Black)
I001945
R
T3
S
T2
C
T1