Operation Section
11
3.5 Air Flow
Air drawn from the right side face passes through the condenser which extracts the heat. This
hot air is blown out through the upper exhaust air duct. Air taken in from the front face is cooled
by the evaporator and then blown through the cool air vent. All the air inlets are equipped with
filters, and the exhaust air duct is protected by metal grill.
3.6 Compressor and Fans
The compressor is hermetically sealed. Two sets of a two-speed fan motor with a centrifugal fan
are used to draw air across the evaporator and condenser.
3.7 Condensate Pump
The condensate pump and a 20 ft (6 m) drain hose are included with the Office Pro 60 to provide
continuous operation without the need of the drain tanks. The condensate pump has a maximum
head lift of 17 ft (5.2 m) at 230 VAC or 13 ft (4.0 m) at 208 VAC.
3.8 Drain Tanks (optional)
A set of two 5.0 gal (19 L) drain tanks are supplied as optional accessory for Office Pro 60. When
drain tanks are used instead of condensate pump, the condensate (water) is collected into both
tanks. The drain switch activates and stops the operation when tanks reach the level of
approximately 8.0 gal (30 L).
I001909
Condenser Air In
Evaporator Air In
Exhaust Air Out