Movincool Office Pro 10 Service Manual Page 29

  • Download
  • Add to my manuals
  • Print
  • Page
    / 56
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 28
TROUBLESHOOTING AND REPAIR
21
In case of trouble, perform the following inspection
before disassembly.
6. Inspection of Plate Fins
To inspect the plate fins of either the evaporator
or condenser you must remove the air filters.
After removal of the air filters, inspect the plate
fins for any dirt, dust, lint, or debris that may have
caused poor cooling performance of the unit. If
cleaning of the fins is necessary, it is recom-
mended that this service be performed by a
qualified service technician.
Plate Fins
Operating Environment
Cooling Capacity
7. Examination of Operating Environment
Operating environments will vary depending on
location, climate and surrounding conditions.
Installation location also can cause operational
problems. Consult your reseller concerning
operational environment requirements.
8. Inspection of Cooling Capacity
Measure the difference in temperature between the
inlet of the evaporator and the cool air vent. If the
difference is out of the range given in the graphs on
page 8, proceed with the possible causes
suggested in the troubleshooting chart on page 24.
COOL
AIR OUT
THERMOMETER
EVAPORATOR
AIR INLET
THERMOMETER
Page view 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 55 56

Comments to this Manuals

No comments