TROUBLESHOOTING AND REPAIR
20
5. Troubleshooting Chart
Unit does not operate at all Check for Power at
Receptacle
•Fan mode DIP switch is set to
“Stop” and current Set Point
Temperature exceeds Room
Temperature
•Fan mode DIP switch is set to
“Stop” and unit has
Condensate Pump that is
defective
Check for Power at Terminal
Block
Check for Power at Relay
Board
Check all wire connections
Defective Drain Tank Switch
Check Relay Board Fuse
Defective or Incorrect Relay
Board
Defective Control Board
Unit starts, but stops immediately Room temperature and
antifreeze thermistor
connectors are reversed on
control board
Defective Fan Motor
Defective Compressor Motor
Defective Relay Board
Unit operates, but stops after a Drain Tank Switch activated
few minutes Fan Mode Switch is set to
“Stop” and unit reached “set
point” temperature so
compressor cycled off
Defective Compressor Motor
Defective Fan Motor
•Fan Mode Switch is set to
“Stop” and compressor
cycled off
Water leakage from the unit Condensate pump not
working
Drain Tank not installed
Drain Tank (if available) is
defective (cracked)
Drain Pan hole is obstructed
Drain hose kinked
Abnormal noise and/or shaking Loose Compressor mounting
nut
Deformed or worn rubber
grommet on the compressor
mounting bolt
Internal interference with
other components
Damaged or out of balance
fan
Trouble Probable Cause
Unit is not responding to control Unit is in the programming mode
board / buttons. No diagnostic and locked out. Press the RUN
code is shown. and SET buttons simultaneously.
Insufficient Air Flow Clogged fins on Evaporator or
Condenser (running unit without
filter(s))
•Fan on “Low” setting
Defective fan motor
Static pressure exceeds design
specifications
Insufficient Cooling Environmental conditions exceed
design specifications
Clogged air filter
Clogged fins
Set point temperature exceeds
room temperature
Defective room temperature
thermistor
Exhaust outlet not properly
ducted
Leak in refrigerant system
Restriction in refrigerant system
Display not working Compressor not operating
Compressor not operating Set point temperature exceeds
room temperature
Unit is operating in Fan Only
Mode (Cool Mode not activated)
Defective Condensate Pump
Defective Compressor Capacitor
Defective Thermistor
Defective Compressor Motor
Check wiring connections
Defective Relay Board
Defective Control Board
Evaporator or Condenser Fan Fan mode DIP switch is set to
Motor(s) not operating “Stop” and current Set Point
Temperature exceeds Room
Temperature
•Fan mode DIP switch is set to
“Stop” and unit has Condensate
Pump that is defective
Check wire connections
Defective fan motor capacitor
Defective fan motor
Defective Relay Board
Defective Control Board