HOSE INSTALLATION
Note: The OP60 is equipped with a
20 foot (6 m) hose.
Connect the 20 foot (6 m) hose to
the drain outlet spout and feed it
through the grommet on the right
hand side of the unit.
Note: Do not use more than 18
feet (5.5 m) of drain hose vertically.
This is the maximum head (lift) of
the Condensate Pump.
When securing the drain hose to the
highest vertical position (no more
than 18 feet (5.5m)) and running the
hose to the drain, run the drain hose
on a downward slope at a rate
minimum of 1/4 inch (6.25 mm) per
foot for proper drainage.
1/4" (6.25 mm)
TAPER PER FOOT
CONDENSATE
PUMP
GROMMET
18' (5.5 m) MAX
DRAIN HOSE
DRAIN STEM
DRAIN HOLE
DRAIN HOSE