TROUBLESHOOTING AND REPAIR
42
LO HI
OPEN OPEN
LO HI
CLOSED CLOSED
VALVE SETTING
LOW PRESSURE
GAUGE READING
VALVE OF
REFRIGERANT
CYLINDER
(OPEN)
LOW PRESSURE VALVE
(CLOSED)
OPEN HIGH PRESSURE VALVE
PROCESS TUBE FITTING
HIGH PRESSURE
SIDE TUBE
LOW PRESSURE
SIDE TUBE
REFRIGERANT
CYLINDER R-22
LOW PRESSURE GAUGE
4 kg/cm
2
G (57 psiG)
4 kg/cm
2
G
(57 psiG)
LO HI
OPEN OPEN
LO HI
CLOSED CLOSED
VALVE SETTING
LOW PRESSURE GAUGE
750 mmHg OR LARGER
GAUGE
LOW PRESSURE
VALVE
VACUUM PUMP
(IN OPERATION)
HIGH PRESSURE
SIDE TUBE
LOW PRESSURE
SIDE TUBE
HIGH PRESSURE VALVE
HIGH PRESSURE GAUGE
AIR PURGING
BLUE
RED
TO PROCESS TUBE FITTING
CHARGING HOSE (GREEN)
OPEN THE VALVE
OF REFRIGERANT
CYLINDER
REFRIGERANT
CYLINDER R-22
LO HI
CLOSED CLOSED
VALVE SETTING
Still Checking Gas Leak
Evacuation
Checking Gas leak
(2) Loosen the nut on the gauge manifold
side of the charging hose (green).
(3) Open the high pressure valve of the
gauge manifold. Charge the system with
refrigerant until the low pressure gauge
indicates 57 PSIG. (4 kg/cm
2
G.) After
charging is complete, close the high
pressure valve.
(4) Check carefully for gas leaks inside the
refrigerant system using the gas leak
tester.
(5) Repair any leak.
WARNING: Do not attempt any repair on a
charged system.
WARNING: Before checking for gas leaks, fully
confirm that there is nothing flammable in the
area to cause an explosion or fire. Contact of
refrigerant with an open fire generates toxic gas.
E. Evacuation (Repeat)
(1) Close the valve of the refrigerant cylinder.
Then remove the charging hose (green)
from the refrigerant cylinder, and connect
it to the refrigerant recovery machine.
NOTE: Keep the high pressure valve and the low
pressure valve of the gauge manifold closed.
(2) Using procedure 28B., evacuate the
system until the low pressure gauge
indicates 750mmHg (30in.HG) or greater.
(For 15 minutes or more.)
(3) After evacuation is complete, close the
high and the low pressure valves of the
gauge manifold.
CAUTION: Be sure to evacuate the system twice
or more using the repetitive vacuum method.
Evacuate the system an additional time on rainy
or humid days.
D. Checking Gas Leak
(1) Remove the charging hose (green) from
the vacuum pump, and connect the hose
to the refrigerant cylinder (R-22).