TROUBLESHOOTING AND REPAIR
38
45º
TUBE
BURNER
BRAZING FILLER METAL
VERTICAL DOWN JOINT
CLEARANCE
0.025 ~ 0.075 mm
FORM THE PIPE FITTING WITH A TUBING TOOL
Vertical Down Joint
Form the Pipe Fitting
BRAZED FITTING AND ITS CLEARANCE
In general, the strength of brazing filler metal
is lower than that of the base metal. So, the
shape and clearance of the brazed fitting are
quite important. As for the shape of the
brazed fitting, it is necessary to maximize its
adhesive area. The clearance of the brazed
fitting must be minimized to facilitate brazing
filler metal to flow into it by capillary action.
CLEANING OF BRAZING FILLER METAL
AND PIPE
When the refrigerant system has been
opened up, exposure to heat may have
caused brazing filler metal to stick to the
inside and outside of the pipe. Brazing filler
metal may also be compounded with oxygen
in the air to form oxide film. Fats and oils may
stick to the pipe from handling. All these
factors will reduce effectiveness of brazing. It
is necessary to eliminate excess brazing filler
metal using sand paper and by cleaning
thoroughly with a solvent such as Trichlene.
26. Inspection
In most cases, the probable cause for insufficient cooling is a clogged system, too much static pressure
refrigerant leakage, or an incorrect amount of refrigerant. In such cases, inspect the system according to
the following procedure.
A. Inspection of Clogged System - Check the component parts of the refrigerant system, including piping,
that could be clogged with refrigerant. If clogged with refrigerant, only the clogged part is frosted
partially. In such a case, change the part in question.
B. Inspection of Refrigerant Leak - Carefully check all connections, and each component for leaks when-
ever the refrigerant system is installed or repaired. Use an electronic gas leak tester to inspect the
system.
C. Insufficient Refrigerant - In case the unit is judged to be deficient in cooling capacity, be sure to perform
the inspections in
26A and 26B to confirm the cause of trouble. After that, charge the system with refrigerant to the
specified amount.
27. Repair of Refrigerant System
In case there is a leak, obstruction, or trouble in the refrigerant system of the Spot Cooling System, replace
or repair the part in question. After replacing any component all connections must be brazed.
A. Proper Brazing Techniques
It is desirable to use a slightly reducing flame. Oxyacetylene is commonly used since it is easy to judge
and adjust the condition of the flame. Unlike gas welding, a secondary flame is used for brazing. It is
necessary to preheat the base metal properly depending on the shape, size or thermal conductivity of
the brazed fitting.
The most important point in flame brazing is to bring the whole brazed fitting to a proper brazing
temperature. Care should be taken to not cause overflow of brazing filler metal, oxidization of brazing
filler metal, or deterioration due to the overheating of flux.