Operation Section
27
5.3 Power Supply Requirements
The unit requires a single-phase 208/230 V, 60 Hz power supply to operate.
• The power supply should be a dedicated single outlet circuit with a UL approved short-circuit
and ground fault protective breaker with a fuse size of 20 A maximum.
Securely tighten each terminal.
The following wire sizes and electrical ratings are recommended:
- Cord Type: SJT (3 wires) or equivalent
- Wire Gauge: 12 AWG
- Voltage Rating: 300 V minimum
- Heat Resistance: 221°F (105°C)
CAUTION
Use a specified 20 A fuse. Do not use wiring, copper wire or soldering instead of the fuse. The
use of non-specified fuses can cause machine failure or fire.
I003159
Circuit Breaker with
Ground-Fault Protection
Ground
Terminal
Terminal Block of Unit
RTG
RTG
Fuse 20 A Max.
T
R
G
Terminal Block
Power Cord