TROUBLESHOOTING AND REPAIR
23
DRAIN HOSE
DRAIN OUTLET SPOUT
GROMMET
1/4" (6.25 mm)
TAPER PER FOOT
CONDENSATE
PUMP
GROMMET
18' (5.5 m) MAX
6. Hose Installation
Note: The OP60 is equipped with a 20 foot (6 m)
hose.
Feed the 20 foot (6m) hose through the grommet on
the right side of the unit and connect to the drain
outlet spout.
Note: Do not use more than 18 feet (5.5 m) of
drain hose vertically. This is the maximum head
(lift) of the Condensate Pump.
When securing the drain hose to the highest vertical
position (no more than 18 feet (5.5m)) and running the
hose to the drain, run the drain hose on a downward
slope at a minimum of 1/4 inch (6.25 mm) per foot for
proper drainage.