Movincool Office Pro 60 Specifications Page 8

  • Download
  • Add to my manuals
  • Print
  • Page
    / 38
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 7
8
INSTALLATION
Choosing an Installation Site
CAUTION: Following are some precautions to consider before
choosing your installation site. Please review carefully as improper
installation may result in personal injury or damage to the unit.
1. Do not use the unit in areas where leakage of flammable gas may occur.
2. Do not use the unit in areas where it is exposed to rain or water.
3. Do not use the unit in an environment which contains excessive amounts of
corrosive gas or vapor.
4. Do not use in areas where the temperature is outside the allowable operating
range.
5. Do not install the unit in sloping areas. The unit may move or topple over even
if the casters are set to the LOCKED position.
6. Install the unit in areas that can with-stand the weight of the unit. The Office
Pro W20 unit weighs approximately 220 lb (100 kg), when the drain tank is full
of water.
7. Allow 18 inch of unobstructed airflow for both the air inlets and outlets.
8. Do not use the unit at condition above 95 °F (35 °C) 60 %RH.
9. Do not use the unit when the supplied water temperature is above 90 °F (32
°C).
10. Make sure that the supplied water source has the minimum flow rate of 4.8 gal/
min (18 L/min) at 7 psi (50 kPa) or more.
11. Supply water pressure limitation is maximum 150 psi (1,034 kPa).
When operating the unit with the water hoses, follow the lower water pressure
limitation of the unit or the optional water hoses.
If supply water pressure is exceeding the pressure limitation, a water pressure
regulating valve must be installed in the water supply line before the unit or
hose connections.
12. Do not use the unit with water which contains a high corrosive factor.
Page view 7
1 2 3 4 5 6 7 8 9 10 11 12 13 ... 37 38

Comments to this Manuals

No comments