OPERATION MANUALCMW30Unit Serial Number Range: 0311XXXXCW3 to Present(From March 2011 to Present)READ THIS MANUAL CAREFULLY FOR INSTRUCTIONS ON CORREC
10INSTALLATION (cont.)Unit Dimensions and Clearance Requirement43.745.4All dimensions are in inches.Unit Weight: 236 lb (107 kg)29.8DIA. 0.63.916.0 DI
11INSTALLATION (cont.)Mounting CMW30 to Roof StructureBe sure to securely anchor the top ends of the suspension rods. Make sure all nuts are tight. Be
12INSTALLATION (cont.)Mounting CMW30 to Roof Structure (cont.)Example of Mounting with Pallet1. Install four (4) suspension rods by suspending them fr
13INSTALLATION (cont.)Mounting CMW30 to Roof Structure (cont.)Example of Mounting with Pallet (cont.)4. Insert the suspension rods through the mountin
14INSTALLATION (cont.)Mounting CMW30 to Roof Structure (cont.)Example of Mounting without Pallet1. Install four (4) suspension rods by suspending them
15INSTALLATION (cont.)Mounting CMW30 to Roof Structure (cont.)Example of Mounting without Pallet (cont.)4. Insert the suspension rods through the moun
16INSTALLATION (cont.)Water Pipe ConnectionWARNING: Before wiring the unit, connect the water line to the unit. To avoid electrical shock, make sure t
17INSTALLATION (cont.)Water Pipe Connection (cont.)Connecting Water Pipes (cont.)4. Make sure the water inlet and outlet of the unit and water source
18INSTALLATION (cont.)Drain Hose ConnectionThe CMW30 is equipped with an internal condensation removal pump with maximum head lift of 4 feet (1.2 m).1
19INSTALLATION (cont.)Drain Hose Connection (cont.)4. Check the following items.• No kinks or bends on the drain hose• No trap in the drain hose• The
SERIAL NUMBER LOCATION AND IDENTIFICATIONNameplate Label PositionNameplate LabelCOOLING AMPS. WITH PUMPCOMPR. OUTPUTREFRIGERANT/TOTAL CHARGEDESIGN PRE
20INSTALLATION (cont.)Drain Hose Connection (cont.)3. Remove the cover plate by removing two (2) screws. Remove the jumper plug from the mating connec
21INSTALLATION (cont.)Packing AttachmentApply the provided packing to the cool air exhaust to prevent condensation in high humidity environments.Remov
22INSTALLATION (cont.)Power Supply and Field Wiring ConnectionWARNING:1. All electrical work should only be performed by qualified personnel. Repair t
23INSTALLATION (cont.)Power Supply and Field Wiring Connection (cont.)Field Wiring ConnectionThe following are recommended wire sizes and electrical r
24INSTALLATION (cont.)Power Supply and Field Wiring Connection (cont.)Field Wiring Connection (cont.)5. Connect the line wire (“R” and “T”) to the ter
25INSTALLATION (cont.)DIP Switch Configuration and Setting (cont.)SwitchNameSwitchNumberFunctionDSW11ON Enables the millivolt wall thermostat.OFF Enab
26INSTALLATION (cont.)Supplied Wall Mounted Controller ConnectionSet up the wall mounted controller without power connection on the unit. Otherwise, t
27INSTALLATION (cont.)Supplied Wall Mounted Controller Connection (cont.)2. Remove four (4) screws from the back cover.3. Connect the supplied shield
28INSTALLATION (cont.)Supplied Wall Mounted Controller Connection (cont.)4. Depending on installation conditions, there are two methods to insert the
29INSTALLATION (cont.)Supplied Wall Mounted Controller Connection (cont.)6. Select the proper location where the controller can be conveniently access
OPERATION MANUALCMW30
30INSTALLATION (cont.)Supplied Wall Mounted Controller Connection (cont.)9. Disconnect power before connecting the wall mounted controller to the unit
31INSTALLATION (cont.)Supplied Wall Mounted Controller Connection (cont.)11. DIP switch #1 of DSW1 on the relay board must be in the OFF position to u
32INSTALLATION (cont.)Field-Supplied Millivolt Wall Thermostat Connection (cont.)1. Use with a single or multi stage system wall thermostat.Thermostat
33INSTALLATION (cont.)Field-Supplied Millivolt Wall Thermostat Connection (cont.)Note: 1. Terminal No. G1 is used only with the wall thermostat that h
34INSTALLATION (cont.)Warning Signal Connection (Output Signal)The unit is equipped with a warning signal output relay type (Form-C, normal open dry c
35INSTALLATION (cont.)Warning Signal Connection (Output Signal) (cont.)Connecting Warning Signal to CMW30 (cont.)4. Connect the warning signal wires t
36INSTALLATION (cont.)Fire Alarm Connection (Input Signal) (cont.)Connecting Fire Alarm Signal to CMW30 (cont.)3. Do not touch the relay board of the
37FEATURES OF CMW301. This unit is equipped with a variable speed compressor, which is driven by state of the art inverter technology. A variable spee
38OPERATION (Wall Mounted Controller ONLY)Control PanelBefore operating the unit, it is important to familiarize yourself with the basic controls loca
39OPERATION (Wall Mounted Controller ONLY) (cont.)Control Panel (cont.)1. ON/OFF Button Activates (LED illuminates green) or deactivates unit operatio
Table of ContentsSERIAL NUMBER LOCATION AND IDENTIFICATION ... 2FOREWORD ...
40OPERATION (Wall Mounted Controller ONLY) (cont.)Control Panel (cont.)Note:1. The room temperature display range is from 16 °F (-9 °C) to 140 °F (60
41OPERATION (Wall Mounted Controller ONLY) (cont.)Standby ModeWhen power source is supplied to the unit, the wall mounted controller is in standby mod
42OPERATION (Wall Mounted Controller ONLY) (cont.)Operate in COOL ModeWhen in COOL mode, the compressor is operated and cool air is circulated.1. Pres
43OPERATION (Wall Mounted Controller ONLY) (cont.)Operate in FAN ONLY ModeWhen in FAN ONLY mode, the unit circulates the surrounding air.1. Press ON/O
44OPERATION (Wall Mounted Controller ONLY) (cont.)Program SettingTo program the controller, read the instructions on page 45 to 47 and follow the flow
45OPERATION (Wall Mounted Controller ONLY) (cont.)Select Program Sequence Number1. Press and hold PROGRAM button for 3 seconds. “Pr 01” blinks.Note: I
46OPERATION (Wall Mounted Controller ONLY) (cont.)Set Stop Time11. Press UP ( ) or DOWN ( ) button to select “Day of the week”.Press ENTER button. “Ho
47OPERATION (Wall Mounted Controller ONLY) (cont.)Edit Program1. Press and hold PROGRAM button for 3 seconds. “Pr 01” blinks.2. Press UP ( ) or DOWN (
48OPERATION (Wall Mounted Controller ONLY) (cont.)Program Plan SheetSTARTPr 01STOPSTARTPr 02STOPSTARTPr 03STOPSTARTPr 04STOPSTARTPr 05STOPSTARTPr 06ST
49SELF-DIAGNOSTIC CODES & BUZZER PATTERNSelf-Diagnostic CodesSelf-diagnostic codes are displayed with “CHECK” on LCD panel of the supplied wall mo
Run and Stop Program ... 47Program Plan Sheet ...
50SELF-DIAGNOSTIC CODES & BUZZER PATTERN (cont.)Table of Self-Diagnostic CodesSelf-Diagnosticcodes(Wall mountedcontroller only)BuzzerPatternCondit
51INSPECTION & MAINTENANCECleaning Air FiltersThe air filter on the evaporator return grill should be checked weekly for dust buildup.Clean or rep
52TROUBLESHOOTINGCheck the following conditions before calling your MovinCool reseller or a qualified technician. If conditions persist after the abov
53TROUBLESHOOTING (cont.)If conditions persist after the above remedies have been performed, turn off the unit, disconnect the power, and contact your
54TROUBLESHOOTING (cont.)If conditions persist after the above remedies have been performed, turn off the unit, disconnect the power, and contact your
55TROUBLESHOOTING (cont.)If conditions persist after the above remedies have been performed, turn off the unit, disconnect the power, and contact your
56TROUBLESHOOTING (cont.)If conditions persist after the above remedies have been performed, turn off the unit, disconnect the power, and contact your
57TROUBLESHOOTING (cont.)If conditions persist after the above remedies have been performed, turn off the unit, disconnect the power, and contact your
58TROUBLESHOOTING (cont.)If conditions persist after the above remedies have been performed, turn off the unit, disconnect the power, and contact your
59TROUBLESHOOTING (cont.)If conditions persist after the above remedies have been performed, turn off the unit, disconnect the power, and contact your
6FOREWORDCongratulations on purchasing the MovinCool air conditioner. This manual explains how to assemble, install and operate the MovinCool CMW30 ai
60TECHNICAL SPECIFICATIONSItem SpecificationsElectronic Features Control Wall Mounted Controller (Included)Set PointTemperature RangeMax. 95 °F (35 °C
61TECHNICAL SPECIFICATIONS (cont.)• Specifications are subject to change without notice.Note:*1: With two 20 feet (6.1 m) ducts containing one 90° ben
WARRANTY STATEMENTDENSO PRODUCTS AND SERVICES AMERICAS, INC. ("DENSO") warrants its MOVINCOOL Products only to the extent stated in its offi
P/N: 484007-3402EN Third Issue: June 2013
7UNPACKINGRemove the package as shown below.Note: The unit can be installed while the unit is on the pallet. (See “Mounting CMW30 to Roof Structure” o
8INVENTORYAfter unpacking your MovinCool unit, please check to make sure you have the following items:1. CMW30 MovinCool Unit (1)2. Operation Manual/P
9INSTALLATIONUnit OverviewILL00253-00COOL AIR EXHAUST(12.0 in. DIA. FLANGE)DRAIN PIPE FOR PUMPEVAPORATOR (ROOM)AIR INTAKE(14.0 in. DIA. FLANGE)MOUNTIN