Movincool CMW30 User Manual

Browse online or download User Manual for Conditioners Movincool CMW30. MovinCool CMW30 User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - OPERATION MANUAL

OPERATION MANUALCMW30Unit Serial Number Range: 0311XXXXCW3 to Present(From March 2011 to Present)READ THIS MANUAL CAREFULLY FOR INSTRUCTIONS ON CORREC

Page 2 - Nameplate Label

10INSTALLATION (cont.)Unit Dimensions and Clearance Requirement43.745.4All dimensions are in inches.Unit Weight: 236 lb (107 kg)29.8DIA. 0.63.916.0 DI

Page 3

11INSTALLATION (cont.)Mounting CMW30 to Roof StructureBe sure to securely anchor the top ends of the suspension rods. Make sure all nuts are tight. Be

Page 4 - Table of Contents

12INSTALLATION (cont.)Mounting CMW30 to Roof Structure (cont.)Example of Mounting with Pallet1. Install four (4) suspension rods by suspending them fr

Page 5

13INSTALLATION (cont.)Mounting CMW30 to Roof Structure (cont.)Example of Mounting with Pallet (cont.)4. Insert the suspension rods through the mountin

Page 6 - FOREWORD

14INSTALLATION (cont.)Mounting CMW30 to Roof Structure (cont.)Example of Mounting without Pallet1. Install four (4) suspension rods by suspending them

Page 7 - UNPACKING

15INSTALLATION (cont.)Mounting CMW30 to Roof Structure (cont.)Example of Mounting without Pallet (cont.)4. Insert the suspension rods through the moun

Page 8 - INVENTORY

16INSTALLATION (cont.)Water Pipe ConnectionWARNING: Before wiring the unit, connect the water line to the unit. To avoid electrical shock, make sure t

Page 9 - ILL00254-00

17INSTALLATION (cont.)Water Pipe Connection (cont.)Connecting Water Pipes (cont.)4. Make sure the water inlet and outlet of the unit and water source

Page 10 - DIA. 12.0

18INSTALLATION (cont.)Drain Hose ConnectionThe CMW30 is equipped with an internal condensation removal pump with maximum head lift of 4 feet (1.2 m).1

Page 11 - Washer (4) 1/2 in

19INSTALLATION (cont.)Drain Hose Connection (cont.)4. Check the following items.• No kinks or bends on the drain hose• No trap in the drain hose• The

Page 12

SERIAL NUMBER LOCATION AND IDENTIFICATIONNameplate Label PositionNameplate LabelCOOLING AMPS. WITH PUMPCOMPR. OUTPUTREFRIGERANT/TOTAL CHARGEDESIGN PRE

Page 13 - ILL00260-00

20INSTALLATION (cont.)Drain Hose Connection (cont.)3. Remove the cover plate by removing two (2) screws. Remove the jumper plug from the mating connec

Page 14

21INSTALLATION (cont.)Packing AttachmentApply the provided packing to the cool air exhaust to prevent condensation in high humidity environments.Remov

Page 15 - ILL00356-00

22INSTALLATION (cont.)Power Supply and Field Wiring ConnectionWARNING:1. All electrical work should only be performed by qualified personnel. Repair t

Page 16 - Connecting Water Pipes

23INSTALLATION (cont.)Power Supply and Field Wiring Connection (cont.)Field Wiring ConnectionThe following are recommended wire sizes and electrical r

Page 17

24INSTALLATION (cont.)Power Supply and Field Wiring Connection (cont.)Field Wiring Connection (cont.)5. Connect the line wire (“R” and “T”) to the ter

Page 18 - Drain Hose Connection

25INSTALLATION (cont.)DIP Switch Configuration and Setting (cont.)SwitchNameSwitchNumberFunctionDSW11ON Enables the millivolt wall thermostat.OFF Enab

Page 19 - Drain Hose Connection (cont.)

26INSTALLATION (cont.)Supplied Wall Mounted Controller ConnectionSet up the wall mounted controller without power connection on the unit. Otherwise, t

Page 20

27INSTALLATION (cont.)Supplied Wall Mounted Controller Connection (cont.)2. Remove four (4) screws from the back cover.3. Connect the supplied shield

Page 21

28INSTALLATION (cont.)Supplied Wall Mounted Controller Connection (cont.)4. Depending on installation conditions, there are two methods to insert the

Page 22 - Power Supply

29INSTALLATION (cont.)Supplied Wall Mounted Controller Connection (cont.)6. Select the proper location where the controller can be conveniently access

Page 24 - ILL00290-00

30INSTALLATION (cont.)Supplied Wall Mounted Controller Connection (cont.)9. Disconnect power before connecting the wall mounted controller to the unit

Page 25 - Function

31INSTALLATION (cont.)Supplied Wall Mounted Controller Connection (cont.)11. DIP switch #1 of DSW1 on the relay board must be in the OFF position to u

Page 26 - WARNING:

32INSTALLATION (cont.)Field-Supplied Millivolt Wall Thermostat Connection (cont.)1. Use with a single or multi stage system wall thermostat.Thermostat

Page 27 - ILL00293-00

33INSTALLATION (cont.)Field-Supplied Millivolt Wall Thermostat Connection (cont.)Note: 1. Terminal No. G1 is used only with the wall thermostat that h

Page 28 - ILL00297-00

34INSTALLATION (cont.)Warning Signal Connection (Output Signal)The unit is equipped with a warning signal output relay type (Form-C, normal open dry c

Page 29 - ILL00299-00

35INSTALLATION (cont.)Warning Signal Connection (Output Signal) (cont.)Connecting Warning Signal to CMW30 (cont.)4. Connect the warning signal wires t

Page 30 - Terminal No

36INSTALLATION (cont.)Fire Alarm Connection (Input Signal) (cont.)Connecting Fire Alarm Signal to CMW30 (cont.)3. Do not touch the relay board of the

Page 31 - Relay Board

37FEATURES OF CMW301. This unit is equipped with a variable speed compressor, which is driven by state of the art inverter technology. A variable spee

Page 32

38OPERATION (Wall Mounted Controller ONLY)Control PanelBefore operating the unit, it is important to familiarize yourself with the basic controls loca

Page 33

39OPERATION (Wall Mounted Controller ONLY) (cont.)Control Panel (cont.)1. ON/OFF Button Activates (LED illuminates green) or deactivates unit operatio

Page 34

Table of ContentsSERIAL NUMBER LOCATION AND IDENTIFICATION ... 2FOREWORD ...

Page 35

40OPERATION (Wall Mounted Controller ONLY) (cont.)Control Panel (cont.)Note:1. The room temperature display range is from 16 °F (-9 °C) to 140 °F (60

Page 36 - SIGNAL WIRE INLET

41OPERATION (Wall Mounted Controller ONLY) (cont.)Standby ModeWhen power source is supplied to the unit, the wall mounted controller is in standby mod

Page 37 - CONTROLLER

42OPERATION (Wall Mounted Controller ONLY) (cont.)Operate in COOL ModeWhen in COOL mode, the compressor is operated and cool air is circulated.1. Pres

Page 38 - 0.6 in (15 mm)

43OPERATION (Wall Mounted Controller ONLY) (cont.)Operate in FAN ONLY ModeWhen in FAN ONLY mode, the unit circulates the surrounding air.1. Press ON/O

Page 39 - OPERATION

44OPERATION (Wall Mounted Controller ONLY) (cont.)Program SettingTo program the controller, read the instructions on page 45 to 47 and follow the flow

Page 40 - Control Panel (cont.)

45OPERATION (Wall Mounted Controller ONLY) (cont.)Select Program Sequence Number1. Press and hold PROGRAM button for 3 seconds. “Pr 01” blinks.Note: I

Page 41

46OPERATION (Wall Mounted Controller ONLY) (cont.)Set Stop Time11. Press UP ( ) or DOWN ( ) button to select “Day of the week”.Press ENTER button. “Ho

Page 42

47OPERATION (Wall Mounted Controller ONLY) (cont.)Edit Program1. Press and hold PROGRAM button for 3 seconds. “Pr 01” blinks.2. Press UP ( ) or DOWN (

Page 43

48OPERATION (Wall Mounted Controller ONLY) (cont.)Program Plan SheetSTARTPr 01STOPSTARTPr 02STOPSTARTPr 03STOPSTARTPr 04STOPSTARTPr 05STOPSTARTPr 06ST

Page 44 - Program Setting

49SELF-DIAGNOSTIC CODES & BUZZER PATTERNSelf-Diagnostic CodesSelf-diagnostic codes are displayed with “CHECK” on LCD panel of the supplied wall mo

Page 45

Run and Stop Program ... 47Program Plan Sheet ...

Page 46

50SELF-DIAGNOSTIC CODES & BUZZER PATTERN (cont.)Table of Self-Diagnostic CodesSelf-Diagnosticcodes(Wall mountedcontroller only)BuzzerPatternCondit

Page 47

51INSPECTION & MAINTENANCECleaning Air FiltersThe air filter on the evaporator return grill should be checked weekly for dust buildup.Clean or rep

Page 48

52TROUBLESHOOTINGCheck the following conditions before calling your MovinCool reseller or a qualified technician. If conditions persist after the abov

Page 49 - Buzzer Pattern

53TROUBLESHOOTING (cont.)If conditions persist after the above remedies have been performed, turn off the unit, disconnect the power, and contact your

Page 50

54TROUBLESHOOTING (cont.)If conditions persist after the above remedies have been performed, turn off the unit, disconnect the power, and contact your

Page 51 - INSPECTION & MAINTENANCE

55TROUBLESHOOTING (cont.)If conditions persist after the above remedies have been performed, turn off the unit, disconnect the power, and contact your

Page 52

56TROUBLESHOOTING (cont.)If conditions persist after the above remedies have been performed, turn off the unit, disconnect the power, and contact your

Page 53 - Cause Remedy

57TROUBLESHOOTING (cont.)If conditions persist after the above remedies have been performed, turn off the unit, disconnect the power, and contact your

Page 54

58TROUBLESHOOTING (cont.)If conditions persist after the above remedies have been performed, turn off the unit, disconnect the power, and contact your

Page 55

59TROUBLESHOOTING (cont.)If conditions persist after the above remedies have been performed, turn off the unit, disconnect the power, and contact your

Page 56

6FOREWORDCongratulations on purchasing the MovinCool air conditioner. This manual explains how to assemble, install and operate the MovinCool CMW30 ai

Page 57

60TECHNICAL SPECIFICATIONSItem SpecificationsElectronic Features Control Wall Mounted Controller (Included)Set PointTemperature RangeMax. 95 °F (35 °C

Page 58

61TECHNICAL SPECIFICATIONS (cont.)• Specifications are subject to change without notice.Note:*1: With two 20 feet (6.1 m) ducts containing one 90° ben

Page 59

WARRANTY STATEMENTDENSO PRODUCTS AND SERVICES AMERICAS, INC. ("DENSO") warrants its MOVINCOOL Products only to the extent stated in its offi

Page 60

P/N: 484007-3402EN Third Issue: June 2013

Page 61

7UNPACKINGRemove the package as shown below.Note: The unit can be installed while the unit is on the pallet. (See “Mounting CMW30 to Roof Structure” o

Page 62 - WARRANTY STATEMENT

8INVENTORYAfter unpacking your MovinCool unit, please check to make sure you have the following items:1. CMW30 MovinCool Unit (1)2. Operation Manual/P

Page 63

9INSTALLATIONUnit OverviewILL00253-00COOL AIR EXHAUST(12.0 in. DIA. FLANGE)DRAIN PIPE FOR PUMPEVAPORATOR (ROOM)AIR INTAKE(14.0 in. DIA. FLANGE)MOUNTIN